phone Phone
+62811100685
close
menu

PT HAITEK CIPTA BERLIAN

sql
Electromagnetic Flowmeter - Model AMF900 Series
Hover to Zoom

Jual Electromagnetic Flowmeter - Model AMF900 Series



Spesifikasi Electromagnetic Flowmeter - Model AMF900 Series

Alat Ukur Tekanan Air (Electromagnetic Flowmeter)

 

Size :

10A,10,15,20, 25,32,40,50,65,80,100,125,150,200,250,300,350,400,450,500,600, 700,800,900,1000,1200,1400,1600, 1800,2000 mm

 

Measuring Range :

Velocity  0 - 0.25 m/s min. / 0 - 12 m/s max.

 

Material :

Measuring Tube : Stainless Steel 304

Flange : Carbon Steel (Standard) / Stainless Steel 304 (Option) / Stainless Steel 316, 316L (Option)

Coil Housing : Carbon Steel (Standard) / Stainless Steel 316,316L (Option)

 

Liner :

Polyurethane (25-400 mm)

Neoprene (50-2000 mm)

FEP (10A-300 mm)

PTFE (10A-2000 mm)

PFA (10A-300 mm)

 

Protection Class :

Junction box IP67, Body IP68

IP 68 (Submersible)

 

Conductivity :

More than 5 uS/cm

 

Explosion Proof :

Exd(ib)ibqIIBT5

(with AMC3100/AMC3200 only)

 

Cable Entry :

Standard :PG11 Option:1/2"NPTF

 

Electrode & Grounding :

Stainless Steel 316L

Hastelloy B

Hastelloy C

Titanium

Tantalum

Platinum

Tungsten Carbide

 

Grounding Electrode :

DN10A/10: use Grounding Ring *1pc

DN15-2000: 3 Electrodes

 

Process Connection :

Flange

 

Flange Type :

JIS 10K / JIS 20K / JIS 40K

ANSI 150# / ANSI 300# / ANSI 600#

DIN PN 10 / PN 16 / PN25 / PN 40

 

Grounding Resistance :

Must be less than 10 W

 

Accuracy :

+/-0.4% of reading (Velocity≥0.5 m/s)

+/-0.0025 m/s (Velocity < 0.5 m/s)

+/-0.2% of reading (Suitable for AMC3200/3100 converter)

 

Temperature :

-10 ~ +60 °C(Polyurethane, PU)

-20 ~ +70 °C(Neoprene)

-40 ~ +120 °C(PTFE 3/8"to 10")

-40~+140 °C(PTFE 3/8"to6", FEP 3/8"to12")

-40~+180 °C(PTFE 3/8"to3", PFA3/8"to12")

 

Ambient Temperature :

-25 to +60 °C

 

Max. Pressure :

350 Kg/cm2

Untuk keterangan lebih lanjut, silahkan download PDF ini :